Scope of application
PVC insulated PVC sheathed control cable is suitable for control, signal, protection and measurement system wiring with rated voltage 450/750V and below or 0.6/1kV and below.

Service characteristics
● Rated power frequency voltage Uo/U is 450/750V or 0.6/1kV.
● The maximum allowable long-term operating temperature of the cable conductor is 70℃.
● When the cable is laid, the ambient temperature should not be lower than 0℃. If the ambient temperature is lower than 0℃, the cable should be preheated.
● The recommended allowable bending radius of the cable is as follows:
Unarmoured cable, should not be less than 6 times the cable diameter;
Armored or copper tape shielded cable, should not be less than 12 times the outer diameter of the cable;
The shielded flexible cable should not be less than 6 times the outer diameter of the cable.