AAAC Aaac Conductor -All Aluminum Alloy Conductor
1.Bare AAAC conductor is usually used for power transmission line project.
2.We are familiar with different international standards with IEC,BS,DIN, ASTM.We an supply very professional service for customer.
3.Packing: in drums in 2000m or 3000m according to customer’s requirement
4.Delivery: about 50km production per day
AAAC Conductor (JLHA1)
Standard: Chinese Standard GB/T 1179-2008
Nominal Aera mm2 | Code Number | Calculated Area mm2 | Number of Wires | Diameter | Rated Strength KN | Max. D.C. Resistance at 20℃ ≤Ω/km | |
Wire mm | OD mm | ||||||
20 | 16 | 18.6 | 7 | 1.84 | 5.52 | 6.04 | 1.7896 |
30 | 25 | 29.0 | 7 | 2.30 | 6.90 | 9.44 | 1.1453 |
45 | 40 | 46.5 | 7 | 2.91 | 8.72 | 15.10 | 0.7158 |
75 | 63 | 73.2 | 7 | 3.65 | 10.9 | 23.06 | 0.4545 |
120 | 100 | 116 | 19 | 2.79 | 14.0 | 37.76 | 0.2877 |
145 | 125 | 145 | 19 | 3.12 | 15.6 | 47.20 | 0.2302 |
185 | 160 | 186 | 19 | 3.53 | 17.6 | 58.56 | 0.1798 |
230 | 200 | 232 | 19 | 3.95 | 19.7 | 73.20 | 0.1439 |
300 | 250 | 290 | 19 | 4.41 | 22.1 | 91.50 | 0.1151 |
360 | 315 | 366 | 37 | 3.55 | 24.8 | 115.29 | 0.0916 |
465 | 400 | 465 | 37 | 4.00 | 28.0 | 146.40 | 0.0721 |
520 | 450 | 523 | 37 | 4.24 | 29.7 | 164.70 | 0.0641 |
580 | 500 | 581 | 37 | 4.47 | 31.3 | 183.00 | 0.0577 |
650 | 560 | 651 | 61 | 3.69 | 33.2 | 204.96 | 0.0516 |
720 | 630 | 732 | 61 | 3.91 | 35.2 | 230.58 | 0.0458 |
825 | 710 | 825 | 61 | 4.15 | 37.3 | 259.86 | 0.0407 |
930 | 800 | 930 | 61 | 4.40 | 39.6 | 292.80 | 0.0361 |
1050 | 900 | 1046 | 91 | 3.83 | 42.1 | 329.40 | 0.0321 |
1150 | 1000 | 1162 | 91 | 4.03 | 44.4 | 366.00 | 0.0289 |
1300 | 1120 | 1301 | 91 | 4.27 | 46.9 | 409.92 | 0.0258 |
AAAC Conductor
Standard: ASTM B399
Code name | Area | No./wire diameter | Overall diameter | Weight | Nominal breaking load | Standard length | |
Nominal | Actual | ||||||
MCM | mm2 | mm | mm | Kg/km | KN | m±5% | |
Akron | 30.58 | 15.48 | 7/1.68 | 5.04 | 42.7 | 4.92 | 3000 |
Alton | 48.69 | 24.71 | 7/2.12 | 6.35 | 68.0 | 7.84 | 3000 |
Ames | 77.47 | 39.22 | 7/2.67 | 8.02 | 108 | 12.45 | 2000 |
Azusa | 123.3 | 62.38 | 7/3.37 | 10.11 | 172 | 18.97 | 2000 |
Anaheim | 155.4 | 78.65 | 7/3.78 | 11.35 | 217 | 23.93 | 3000 |
Amherst | 195.7 | 99.22 | 7/4.25 | 12.75 | 273 | 30.18 | 2500 |
Alliance | 246.9 | 125.1 | 7/4.77 | 14.31 | 345 | 38.05 | 2000 |
Butte | 312.8 | 158.6 | 19/3.26 | 16.30 | 437 | 48.76 | 3000 |
Canton | 394.5 | 199.9 | 19/3.66 | 18.30 | 551 | 58.91 | 2500 |
Cairo | 465.4 | 235.8 | 19/3.98 | 19.88 | 650 | 69.48 | 2000 |
Darien | 559.5 | 283.5 | 19/4.36 | 21.79 | 781 | 83.52 | 2000 |
Elgin | 652.4 | 330.6 | 19/4.71 | 23.54 | 911 | 97.42 | 1500 |
Flint | 740.8 | 375.3 | 37/3.59 | 25.16 | 1035 | 108.21 | 3000 |
Greely | 927.2 | 469.8 | 37/4.02 | 28.14 | 1295 | 135.47 | 2500 |
AAAC conductor
Standard: ASTM B399
Area | No./wire diameter | Overall diameter | Weight | Nominal breaking load | Max D.C. resistance at 20℃ | Standard length | |
Nominal | Actual | ||||||
AWG or MCM | mm2 | mm | mm | Kg/km | KN | Ω/km | m±5% |
6 | 13.30 | 7/1.554 | 4.67 | 37 | 4.22 | 2.5199 | 3500 |
4 | 21.15 | 7/1.961 | 5.89 | 58 | 6.71 | 1.5824 | 3000 |
2 | 33.63 | 7/2.474 | 7.42 | 93 | 10.68 | 0.9942 | 2500 |
1/0 | 53.48 | 7/3.119 | 9.36 | 148 | 16.97 | 0.6256 | 2000 |
2/0 | 67.42 | 7/3.503 | 10.51 | 186 | 20.52 | 0.4959 | 3500 |
3/0 | 85.03 | 7/3.932 | 11.80 | 234 | 25.86 | 0.3939 | 3000 |
4/0 | 107.23 | 7/4.417 | 13.26 | 296 | 32.63 | 0.3119 | 2000 |
250 | 126.66 | 19/2.913 | 14.57 | 349 | 38.93 | 0.2642 | 2000 |
300 | 152.10 | 19/3.193 | 15.97 | 419 | 46.77 | 0.2199 | 3000 |
350 | 177.35 | 19/3.447 | 17.24 | 489 | 52.25 | 0.1887 | 3000 |
400 | 202.71 | 19/3.686 | 18.43 | 559 | 59.74 | 0.1650 | 2500 |
450 | 228.00 | 19/3.909 | 19.66 | 629 | 67.19 | 0.1467 | 2000 |
500 | 253.35 | 19/4.120 | 20.60 | 698 | 74.64 | 0.1321 | 2000 |
550 | 278.60 | 37/3.096 | 21.67 | 768 | 83.80 | 0.1202 | 2000 |
600 | 303.80 | 37/3.233 | 22.63 | 838 | 91.38 | 0.1102 | 2000 |
650 | 329.25 | 37/3.366 | 23.56 | 908 | 97.94 | 0.1016 | 2000 |
700 | 354.55 | 37/3.493 | 24.45 | 978 | 102.20 | 0.0944 | 3500 |
750 | 380.20 | 37/3.617 | 25.32 | 1049 | 109.60 | 0.0880 | 3000 |
800 | 405.15 | 37/3.734 | 26.14 | 1117 | 116.80 | 0.0826 | 3000 |
900 | 456.16 | 37/3.962 | 27.73 | 1258 | 131.50 | 0.0733 | 3000 |
1000 | 506.71 | 37/4.176 | 29.23 | 1399 | 146.10 | 0.0660 | 2500 |
AAAC Conductor Cable
Standard: BS EN50183
Code name | Calculated area | No of wires | Diameter | Weight | Rated strength | Max D.C. resistance at 20℃ | |
Wire | Cond | ||||||
mm2 | mm | mm | Kg/km | KN | Ω/km | ||
Box | 18.8 | 7 | 1.85 | 5.55 | 51.4 | 5.55 | 1.7480 |
Acacia | 23.8 | 7 | 2.08 | 6.24 | 64.9 | 7.02 | 1.3828 |
Almond | 30.1 | 7 | 2.34 | 7.02 | 82.2 | 8.88 | 1.0926 |
Cedar | 35.5 | 7 | 2.54 | 7.62 | 96.8 | 10.46 | 0.9273 |
Deodar | 42.2 | 7 | 2.77 | 8.31 | 115.2 | 12.44 | 0.7797 |
Fir | 47.8 | 7 | 2.95 | 8.85 | 130.6 | 14.11 | 0.6875 |
Hazel | 59.9 | 7 | 3.30 | 9.90 | 163.4 | 17.66 | 0.5494 |
Pine | 71.6 | 7 | 3.61 | 10.8 | 195.6 | 21.14 | 0.4591 |
Holly | 84.1 | 7 | 3.91 | 11.7 | 229.5 | 24.79 | 0.3913 |
Willow | 89.7 | 7 | 4.04 | 12.1 | 245.0 | 26.47 | 0.3665 |
Oak | 118.9 | 7 | 4.65 | 14.0 | 324.5 | 65.07 | 0.2767 |
Mulberry | 150.9 | 19 | 3.18 | 15.9 | 414.3 | 44.52 | 0.2192 |
Ash | 180.7 | 19 | 3.48 | 17.4 | 496.1 | 53.31 | 0.1830 |
Elm | 211.0 | 19 | 3.76 | 18.8 | 579.2 | 62.24 | 0.1568 |
Poplar | 239.4 | 37 | 2.87 | 20.1 | 659.4 | 70.61 | 0.1387 |
Sycamore | 303.2 | 37 | 3.23 | 22.6 | 835.2 | 89.40 | 0.1095 |
Upas | 362.1 | 37 | 3.53 | 24.7 | 997.5 | 106.82 | 0.0917 |
Yew | 479.0 | 37 | 4.06 | 28.4 | 1319.6 | 141.31 | 0.0693 |
Totara | 498.1 | 37 | 4.14 | 29.0 | 1372.1 | 145.93 | 0.0666 |
Rubus | 586.9 | 61 | 3.50 | 31.5 | 1622.0 | 173.13 | 0.0567 |
Sorbus | 659.4 | 61 | 3.71 | 33.4 | 1822.5 | 194.53 | 0.0505 |
Araucaria | 821.1 | 61 | 4.14 | 37.3 | 2269.4 | 242.24 | 0.0406 |
Redwood | 996.2 | 61 | 4.56 | 41.0 | 2753.2 | 293.88 | 0.0334 |
AAAC
Standard: BS 3242
Code name | Nominal area | No of wires | Diameter | Weight | Rated strength | Max D.C. resistance at 20℃ | |
Wire | Cond | ||||||
mm2 | mm | mm | Kg/km | KN | Ω/km | ||
Box | 15 | 7 | 1.85 | 5.55 | 51 | 5.37 | 1.7495 |
Acacia | 20 | 7 | 2.08 | 6.24 | 65 | 6.80 | 1.3840 |
Almond | 25 | 7 | 2.34 | 7.02 | 82 | 8.61 | 1.0934 |
Cedar | 30 | 7 | 2.54 | 7.62 | 97 | 10.14 | 0.9281 |
- | 35 | 7 | 2.77 | 8.31 | 115 | 12.05 | 0.7804 |
Fir | 40 | 7 | 2.95 | 8.85 | 131 | 13.67 | 0.6880 |
Hazel | 50 | 7 | 3.30 | 9.90 | 164 | 17.11 | 0.5498 |
Pine | 60 | 7 | 3.61 | 10.83 | 196 | 20.48 | 0.4594 |
- | 70 | 7 | 3.91 | 11.73 | 230 | 24.02 | 0.3917 |
Willow | 75 | 7 | 4.04 | 12.12 | 245 | 25.65 | 0.3669 |
- | 80 | 7 | 4.19 | 12.57 | 264 | 27.58 | 0..3441 |
- | 90 | 7 | 4.44 | 13.32 | 298 | 31.12 | 0.3023 |
Oak | 100 | 7 | 4.65 | 13.95 | 325 | 33.98 | 0.2769 |
- | 100 | 19 | 2.82 | 14.1 | 326 | 33.93 | 0.2787 |
Mulberry | 125 | 19 | 3.18 | 15.9 | 415 | 43.12 | 0.2192 |
Ash | 150 | 19 | 3.48 | 17.4 | 497 | 51.64 | 0.1831 |
Elm | 175 | 19 | 3.76 | 18.8 | 580 | 60.30 | 0.1568 |
Poplar | 200 | 37 | 2.87 | 20.09 | 659 | 88.41 | 0.1385 |
- | 225 | 37 | 3.05 | 21.35 | 744 | 77.24 | 0.1227 |
Sycamore | 250 | 37 | 3.22 | 22.54 | 835 | 86.64 | 0.1093 |
Upas | 300 | 37 | 3.53 | 24.71 | 997 | 103.50 | 0.09156 |
Walnut | 350 | 37 | 3.81 | 26.67 | 1162 | 120.53 | 0.07860 |
Yew | 400 | 37 | 4.06 | 28.42 | 1319 | 136.85 | 0.06921 |
Totara | 425 | 37 | 4.14 | 28.98 | 1372 | 142.33 | 0.06656 |
Rubus | 500 | 61 | 3.50 | 31.5 | 1620 | 167.71 | 0.05662 |
Sorbus | 659.4 | 61 | 3.71 | 33.4 | 1822.5 | 194.53 | 0.0505 |
Araucaria | 700 | 61 | 4.14 | 37.26 | 2266 | 234.50 | 0.04047 |
AAAC
Standard: DIN 48201
Code number | Calculated area | No of wires | Diameter | Weight | Rated tensile strength | Max D.C. resistance at 20℃ | |
Wire | Cond | ||||||
mm2 | mm2 | mm | mm | Kg/km | daN | Ω/km | |
16 | 15.89 | 7 | 1.70 | 5.1 | 43 | 444 | 2.0910 |
25 | 24.25 | 7 | 2.10 | 6.3 | 66 | 677 | 1.3703 |
35 | 34.36 | 7 | 2.50 | 7.5 | 94 | 960 | 0.9669 |
50 | 49.48 | 7 | 3.00 | 9.0 | 135 | 1382 | 0.6714 |
50 | 48.35 | 19 | 1.80 | 9.0 | 133 | 1350 | 0.6905 |
70 | 65.81 | 19 | 2.10 | 10.5 | 181 | 1838 | 0.5073 |
95 | 93.27 | 19 | 2.50 | 12.5 | 256 | 2605 | 0.3579 |
120 | 116.99 | 19 | 2.80 | 14.0 | 322 | 3268 | 0.2854 |
150 | 147.11 | 37 | 2.25 | 15.8 | 406 | 4109 | 0.2274 |
185 | 181.62 | 37 | 2.50 | 17.5 | 500 | 5073 | 0.1842 |
240 | 242.54 | 61 | 2.25 | 20.3 | 670 | 6774 | 0.1383 |
300 | 299.43 | 61 | 2.50 | 22.5 | 827 | 8363 | 0.1120 |
400 | 400.14 | 61 | 2.89 | 26.0 | 1104 | 11176 | 0.0838 |
500 | 499.63 | 61 | 3.23 | 29.1 | 1379 | 13960 | 0.06709 |
625 | 626.20 | 91 | 2.96 | 32.6 | 1732 | 17490 | 0.0540 |
800 | 802.09 | 91 | 3.35 | 36.9 | 2218 | 22402 | 0.0418 |
1000 | 999.71 | 91 | 3.74 | 41.1 | 2767 | 27922 | 0.0335 |
AAAC(Characteristics of A2 Conductors)
Standard: IEC 61089
Code Number | Calculated Area | Number of Wires | Diameter of Wire | Diameter of Cond. | Linear Mass | Rated Strength | Max.D.C. Resistance At 20℃ |
mm2 | mm2 | mm | mm | kg/km | kN | Ω/km | |
16 | 18.4 | 7 | 1.83 | 5.49 | 50.4 | 5.43 | 1.7896 |
25 | 28.8 | 7 | 2.29 | 6.87 | 78.7 | 8.49 | 1.1453 |
40 | 46.0 | 7 | 2.89 | 8.67 | 125.9 | 13.58 | 0.7158 |
63 | 72.5 | 7 | 3.63 | 10.8 | 198.3 | 21.39 | 0.4545 |
100 | 115 | 19 | 2.78 | 13.9 | 316.3 | 33.95 | 0.2877 |
125 | 144 | 19 | 3.10 | 15.5 | 395.4 | 42.44 | 0.2302 |
160 | 184 | 19 | 3.51 | 17.55 | 506.1 | 54.32 | 0.1798 |
200 | 230 | 19 | 3.93 | 19.65 | 632.7 | 67.91 | 0.1439 |
250 | 288 | 19 | 4.39 | 21.95 | 790.8 | 84.68 | 0.1151 |
315 | 363 | 37 | 3.53 | 24.71 | 998.9 | 106.95 | 0.0916 |
400 | 460 | 37 | 3.98 | 27.86 | 1268.4 | 135.81 | 0.0721 |
450 | 518 | 37 | 4.22 | 29.54 | 1426.9 | 152.79 | 0.0641 |
500 | 575 | 37 | 4.45 | 31.15 | 1585.5 | 169.76 | 0.0577 |
560 | 645 | 61 | 3.67 | 33.03 | 1778.4 | 190.14 | 0.0516 |
630 | 725 | 61 | 3.89 | 35.01 | 2000.7 | 213.90 | 0.0458 |
710 | 817 | 61 | 4.13 | 37.17 | 2254.8 | 241.07 | 0.0407 |
800 | 921 | 61 | 4.38 | 39.42 | 2540.6 | 271.62 | 0.0361 |
900 | 1036 | 91 | 3.81 | 41.91 | 2861.1 | 305.58 | 0.0632 |
1000 | 1151 | 91 | 4.01 | 44.11 | 3179.0 | 339.53 | 0.0289 |
1120 | 1289 | 91 | 4.25 | 46.75 | 3560.5 | 380.27 | 0.0258 |
1252 | 1439 | 91 | 4.49 | 49.39 | 3973.7 | 424.41 | 0.0231 |
AAAC(Characteristics of A3 Conductors)
Standard : IEC 61089
Code Number | Calculated Area | Number of Wires | Diameter of Wire | Diameter of Cond. | Linear Mass | Rated Strength | Max.D.C. Resistance At 20℃ |
mm2 | mm2 | mm | mm | kg/km | kN | Ω/km | |
16 | 18.6 | 7 | 1.84 | 5.52 | 50.8 | 6.04 | 1.7896 |
25 | 29.0 | 7 | 2.30 | 6.90 | 79.5 | 9.44 | 1.1453 |
40 | 46.5 | 7 | 2.91 | 8.73 | 127.1 | 15.10 | 0.7158 |
63 | 73.2 | 7 | 3.65 | 10.95 | 200.2 | 23.06 | 0.4545 |
100 | 116 | 19 | 2.79 | 13.95 | 319.3 | 37.76 | 0.2877 |
125 | 145 | 19 | 3.12 | 15.6 | 399.2 | 47.20 | 0.2302 |
160 | 186 | 19 | 3.53 | 17.65 | 511.0 | 58.56 | 0.1798 |
200 | 232 | 19 | 3.95 | 19.75 | 638.7 | 73.20 | 0.1439 |
250 | 290 | 19 | 4.41 | 22.05 | 798.4 | 91.50 | 0.1151 |
315 | 366 | 37 | 3.55 | 24.85 | 1008.4 | 115.29 | 0.0916 |
400 | 465 | 37 | 4.00 | 28.0 | 1280.5 | 146.40 | 0.0721 |
450 | 523 | 37 | 4.24 | 29.68 | 1440.5 | 164.70 | 0.0641 |
500 | 581 | 37 | 4.47 | 31.29 | 1600.6 | 183.00 | 0.0577 |
560 | 651 | 61 | 3.69 | 33.21 | 1795.3 | 204.95 | 0.0516 |
630 | 732 | 61 | 3.91 | 35.19 | 2019.8 | 230.58 | 0.0458 |
710 | 825 | 61 | 4.15 | 37.35 | 2276.2 | 259.86 | 0.0407 |
800 | 930 | 61 | 4.40 | 39.6 | 2564.8 | 292.80 | 0.0361 |
900 | 1046 | 91 | 3.83 | 42.13 | 2888.3 | 329.40 | 0.0321 |
1000 | 1162 | 91 | 4.03 | 44.33 | 3209.3 | 366.00 | 0.0289 |
1120 | 1301 | 91 | 4.27 | 46.97 | 3594.4 | 409.92 | 0.0258 |